Friday, November 24, 2017

Contact Brand Master

MODULE IMPULSE-20

They are used for fire protection of volumes up to 30 m3. As a rule, small rooms of server rooms, archives, electrical boards, depositories, machine sections of elevators are protected.

 

MODULE IMPULSE-20

ТЕCHNICAL CHARACTERISTICS

Working pressure, at the temperature 20°C±2°C bar 25,0
Maximum / minimum filling kg

HFC 125

19,0 / 11,0

HFC 227ea

21,0 / 11,0

FK-5-1-12

21,0 / 11,0

Discharge time s 10
Operation temperature  0С - 10  to +50
Minimum service life years 10

Marking when ordering:

GFFM Impulse -20 (25 -22,5 -18) Х COMPLETENESS  
1 2 3 4 5 6    

1. gas fire-fighting module;

2. module type;

3. operating pressure, bar (at 20 °С temperature);

4. nominal volume of module cylinder, l;

5. DN valve, mm;

6. type of module attachment (С – ceiling; Н – wall);

Filled module 1 pcs
Mounting bracket (wall or ceiling type) 1 pcs
Manual 1 pcs
Transport package 1 pcs

 

GENERAL VIEW OF «IMPULSE-20» MODULE
ceiling mounting bracket  wall mounting bracket
MODULE IMPULSE-20 Module Impulse-20

1 - module cylinder, 2 - valve, 3 - fixing bolt, 4 - mounting bracke

MOUNTING BRACKET
Ceiling mounting bracket Wall mounting bracket

Ceiling mounting bracket КРС.І - 20

Wall mounting bracket КРН.І - 20 

Warranty 2 years from the date of manufacture.