It is used for fire extinguishing the volume of electrical cabinets, false ceilings, raised floor. Pipe modification module allows you to place the module outside the protected volume and feed the fire extinguishing agent through the hose through the nozzles.
MODULE IMPULSE-2
ТЕCHNICAL CHARACTERISTICS |
||||
Working pressure, at the temperature 20°C±2°C | bar | 25,0 | ||
Maximum / minimum filling | kg |
HFC 125 1,9 / 1,1 |
HFC 227ea 2,1 / 1,1 |
FK-5-1-12 2,1 / 1,1 |
Discharge time | s | 10 | ||
Operation temperature | 0С | - 10 to +50 | ||
Minimum service life | years | 10 |
Marking when ordering:
GFFM | Impulse -2-T | (25 | -2,2 | -18) | Х | COMPLETENESS | |
1 | 2 | 3 | 4 | 5 | 6 | ||
1. gas fire-fighting module; 2. module type; 3. operating pressure, bar (at 20 °С temperature); 4. nominal volume of module cylinder, l; 5. DN valve, mm; 6. type of module attachment (С – ceiling; Н – wall); |
Filled module | 1 pcs | |||||
Mounting bracket (wall or ceiling type) | 1 pcs | ||||||
Manual | 1 pcs | ||||||
Transport package | 1 pcs | ||||||
High pressure hose РВТ-16-П-ХХХ |
Ordered in addition | ||||||
Nozzle (НР-С-176-G1/2" or НР-Н-176-G1/2") | Ordered in addition |
Warranty 2 years from the date of manufacture.